LINETRAXX® NGRM550

The NGRM550 Neutral Grounding Resistor Monitor detects grounding-resistor failures and ground faults. It is intended for use in low-resistance grounded transformers and generators used in commercial and industrial power systems. In these systems, the NGRM550 monitors:

  • Current through the neutral-grounding resistor
  • Voltage between the star point of the transformer and ground (voltage drop across the NGR)
  • NGR failure (open), including failure of connections between neutral and ground

A benefit to many users is the multilingual user interface that allows the comfort of reading values and programming in your native language.

It is an ideal solution that is easy to retrofit into existing LRG applications or factory-install in new LRG packages. If customers prefer, they can easily program the relay via the built-in webserver.  NGRM550’s can easily connect to a supervisory system with Modbus TCP/IP or RTU communications. Capabilities extend to 25 kV and 2,000 A.

NGRM550

The NGRM550 Neutral Grounding Resistor Monitor detects grounding-resistor failures and ground faults. It is intended for use in low-resistance grounded transformers and generators used in commercial and industrial power systems. In these systems, the NGRM550 monitors:

  • Current through the neutral-grounding resistor
  • Voltage between the star point of the transformer and ground (voltage drop across the NGR)
  • NGR failure (open), including failure of connections between neutral and ground

A benefit to many users is the multilingual user interface that allows the comfort of reading values and programming in your native language.

It is an ideal solution that is easy to retrofit into existing LRG applications or factory-install in new LRG packages. If customers prefer, they can easily program the relay via the built-in webserver.  NGRM550’s can easily connect to a supervisory system with Modbus TCP/IP or RTU communications. Capabilities extend to 25 kV and 2,000 A.

Kenmerken

  • Determination of RNGR with passive and active measurement methods
  • Continuous monitoring of the RNGR even if the installation is de-energized
  • Alarm or trip on ground fault
  • Monitoring of the current INGR
  • Monitoring of the voltage UNGR
  • Ethernet communication
  • Webserver
  • Language selection (English, German, Spanish, French)
  • Test button (internal, external) with/without tripping
  • FFT analysis of the measuring signals
  • Relay for detection of ground faults and resistor faults
  • Relay for shutdown of the installation after a configurable time
  • Can be combined with RCMS… for automatic shutdown of feeders
  • Graphical user interface
  • Wide supply voltage range
  • Range of use up to 2,000 m AMSL
  • Fault/history memory
  • Analog output of measured values (0…10 V, 4…20 mA, etc., selectable parameters)
  • Password protection
  • Tripping on RMS, fundamental component signal or harmonics
  • Detection of AC and DC ground faults

LINETRAXX® NGRM550 Variant(en)

TypeSupply voltage US / Frequency range HzArt. No.
NGRM550AC 48…240 V, 40…70 Hz
DC 48…240 V
B94013550

Optionele accessoires voor LINETRAXX® NGRM550

CD-series coupling device

TypeVoltage UsysArt. No.
CD1000400…690 VB98039010
CD1000-2400…1000 VB98039053
CD50001000…4200 VB98039011
CD144004300…14550 VB98039054
CD2500014551…25000 VB98039055

Measuring current transformer

TypeVoltage/CurrentArt. No.
W20AC up to 10 AB98080003
W35
W60
W0-S20
W1-S35
W2-S70
AC up to 25 AB98080010
B98080018
B911787
B911731
B911732
CTUB103-CTBC35AC/DC up to 10 AB78120030
CTUB103-CTBC60
CTUB103-CTBC120
AC/DC up to 25 AB78120031
B78120032

Voltage supply for measuring current transformers CTUB103…

Typemax. connected measuring current transformersArt. No.
STEP-PS/1 AC/24 DC/0.52B94053110
STEP-PS/1 AC/24 DC/1.757B94053111
STEP-PS/1 AC/24 DC/4.217B94053112

Downloads voor LINETRAXX® NGRM550

TypeNaamMaatTaalTijdstempelD-/B-Nummer
Flyers NGR Product Comparison 630.6 KB EN2022/07/18 16:05:0218.07.2022 16:05:02
Handboeken NGRM…-Modbus 453.9 KB DE2022/06/09 10:45:4109.06.2022 10:45:41D00292
Handboeken NGRM…-Modbus 443.2 KB EN2022/06/09 10:47:4409.06.2022 10:47:44D00292
Handboeken NGRM…-Modbus 463.4 KB ES2022/06/09 10:49:2509.06.2022 10:49:25D00292
Gegevensbladen NGRM500/NGRM550 1.2 MB DE2023/03/16 11:55:3216.03.2023 11:55:32D00373
Gegevensbladen NGRM500/NGRM550 1.2 MB FR2023/03/16 11:57:4116.03.2023 11:57:41D00373
Gegevensbladen NGRM500/NGRM550 1.2 MB EN2023/03/16 11:56:2516.03.2023 11:56:25D00373
Beknopte handleidingen NGRM500/NGRM550 1.2 MB DE2022/12/02 11:08:2702.12.2022 11:08:27D00373
Beknopte handleidingen NGRM500/NGRM550 1.5 MB EN2022/12/02 11:08:2802.12.2022 11:08:28D00373
Handboeken NGRM500/NGRM550 5.5 MB DE2022/12/02 11:07:2702.12.2022 11:07:27D00373
Handboeken NGRM500/NGRM550 5.4 MB EN2022/12/02 11:07:5302.12.2022 11:07:53D00373
Technische informatie NGR Checklist (US) 245.3 KB EN2022/11/07 16:39:0207.11.2022 16:39:02
Flyers NGRM550 & NGRM750 630.6 KB EN2022/05/25 06:07:5225.05.2022 06:07:52
Flyers NGRM550 & NGRM750 597.5 KB ES2022/05/25 06:07:5825.05.2022 06:07:58