ISOMETER® IR427 met MK7

ISOMETER® IR427 met MK7

  • Isolatiebewakingsapparaat voor medische IT-systemen
  • Last- en temperatuurbewaking voor IT-systeemtransformator
  • Volgens DIN VDE 0100-710 en DIN EN 61557-8
  • Twee afzonderlijk instelbare drempelwaarden
  • Multifunctioneel LCD-scherm

De ISOMETER® IR427 bewaakt de isolatieweerstand van ongeaarde AC circuits (medische IT-systemen). Tegelijkertijd kan de IT-systeemtransformator worden bewaakt op laststroom en overmatige temperatuur.

  • Kenmerken
  • Toepassingen
  • Accessoires
  • Bestelgegevens
  • Downloads
  • ISOMETER® IR427
  • Insulation monitoring for medical IT systems
  • Load and temperature monitoring for IT system transformers
  • Adjustable response value for R
  • Adjustable load current response value
  • Integrated voltage monitoring for four alarm and test combinations MK7
  • Temperature monitoring via PTC Thermistor or Bimetal switch (NC)
  • Connection monitoring earth
  • LEDs: Power On, Alarm 1, Alarm 2
  • Internal/external test button
  • Programmable alarm relay: N/O or N/C operation
  • Self monitoring with automatic alarm message
  • Compact two-module enclosure (36 mm)
  • Four-wire interface for four alarm and test combinations MK7
  • Remote alarm indicator and test combination MK7
  • Easy-to-clean front foil surface
  • Label field
  • Panel frame alpine white
  • Alarm LEDs: Power On, insulation fault overload, overtemperature
  • Test button
  • Mute button
  • Standard flush-mounting enclosure 66 mm
  • Medical IT systems in accordance with IEC 60364-7-710:2002-11, IEC 61557-8 and DIN VDE 0100-710

 

Optionele accessoires voor ISOMETER® IR427 met MK7


TypeArt. No.
STW2 measuring current transformerB942709
ES0107/temperature sensor (PTC)B924186
XM420 Mounting frameB990994
MK-Cavity-wall-box-60mmB95100203

Varianten van ISOMETER® IR427 met MK7


TypeSupply voltage USArt. No.**
IR427-2AC 70…264 V, 42…460 Hz*B72075300
B92075300
MK7DC 18…28 VB95100201
* Absolute values
**(B7… = push-wire terminal / B9… = screw-type terminal)